Data Aire DAFC-17 Manual de usuario

Busca en linea o descarga Manual de usuario para Acondicionadores de aire del sistema de división Data Aire DAFC-17. DB-AIRE - Dunham Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir

Indice de contenidos

Pagina 1 - 50/60 Hz

FORM NO: MS0701ADB-TEMP SYSTEMSDB-AIRE SYSTEMSPRECISION ENVIRONMENTAL CONTROL UNIT50/60 HzDB-AIRE

Pagina 2 - DB-AIREDB-AIRE

DB-TEMP SYSTEMSWATER COOLED PERFORMANCE DATAPERFORMANCE AT 29.4°C (85°F) ENTERING WATER TEMPERATURENET CAPACITY KW AT STANDARD AIRFLOWMODEL DBTWD/U-0

Pagina 3 - GENERAL INFORMATION

DB-TEMP SYSTEMSREHEAT SECTIONMODEL DBT*D/U-02 DBT*D/U-03 DBT*D/U-04 DBT*D/U-05 DBT*D/U-07 DBT*D/U-09 DBT*D/U-11 DBT*D/U-13STANDARD ELECTRIC KWMBH6.020

Pagina 4 - DB-AIRE MONITORING/ CONTROL

DB-TEMP SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED ELECTRICAL DATAELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFICATION)MO

Pagina 5

DB-TEMP SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED/ CHILLED WATERDIMENSIONAL DATA MODEL 2, 3, 4, 5 TON (UP FLOW) MODEL 2, 3, 4, 5 TON (DOWN FLOW)NOTE

Pagina 6

DB-TEMP SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATA MODEL 07, 09, 11, 13 TON (UP FLOW) MODEL 07, 09, 11, 13 TON (DOWN FLOW)NOTES : 1.

Pagina 7 - NETWORK MONITORING (OPTIONAL)

DB-AIRE DESIGN FEATURESDB-AIRE MODELS9 - 26 TONS32 - 91 KWAIR COOLEDWATER/GLYCOL COOLEDFRAME AND CABINETThe heliarc welded tubular steel frame provide

Pagina 8 - DB-TEMP DESIGN FEATURES

DB-AIRE DESIGN FEATURESCOMPRESSORIZED SYSTEMSThe refrigeration system uses two(2) highlyefficient and quiet scroll compressors. The scrollcompressor h

Pagina 9

DB-AIRE SYSTEMSWATER COOLED PERFORMANCE DATAPERFORMANCE AT 29.4°C (85°F) ENTERING WATER TEMPERATURENET CAPACITY KW AT STANDARD AIRFLOWMODEL DBWD/U-09

Pagina 10 - DB-TEMP SYSTEMS

DB-AIRE SYSTEMSREHEAT SECTIONMODEL DB*D/U-09 DB*D/U-11 DB*D/U-13 DB*D/U-14 DB*D/U-16 DB*D/U-19 DB*D/U-22 DB*D/U-26STANDARD ELECTRIC KWMBH15.051.215.05

Pagina 11

DB-AIRE SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED ELECTRICAL DATAELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFICATION)MO

Pagina 12

DB-AIREDB-AIREPrecision Environmental Control Systems For Computer Rooms.DB-AIRE SYSTEMSState-of-the-art design with microprocessor based liquid cryst

Pagina 13

DB-AIRE SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATAMODEL 9, 11, 13 TON(UP FLOW)MODEL 14, 16, 19, 22, 26 TON(UP FLOW)NOTES : 1.) MINIMUM S

Pagina 14

DB-AIRE SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED DIMENSIONAL DATAMODEL 9, 11, 13 TON(DOWN FLOW)MODEL 14, 16, 19, 22, 26 TON(DOWN FLOW)NOTES : 1.) MINIM

Pagina 15 - DB-AIRE DESIGN FEATURES

CHILLED WATER DESIGN FEATURESDB-TEMP MODELSDB-AIRE MODELSFRAME AND CABINETThe heliarc welded structural steel frameprovides for maximum strength and

Pagina 16 - DB-AIRE SYSTEMS

DB-TEMP CHILLED WATER SYSTEMSCHILLED WATER PERFORMANCE DATAPERFORMANCE WITH 7.2°C (45°F) CHILLED WATER AT SPECIFIED FLOW RATECAPACITY DATA (kW) AT 7.2

Pagina 17

DB-TEMP CHILLED WATER SYSTEMSBLOWER DATAMODEL DBTCD/U-02 DBTCD/U-03 DBTCD/U-04 DBTCD/U-05STANDARD AIR VOLUME CMHCFM17001000255015003400200042502500STA

Pagina 18

DB-TEMP CHILLED WATER SYSTEMSCHILLED WATER ELECTRICAL DATAELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFIER)MODEL DBTCD

Pagina 19

DB-AIRE CHILLED WATER SYSTEMSCHILLED WATER PERFORMANCE DATAPERFORMANCE WITH 7.2°C(45°F) CHILLED WATER AT SPECIFIED FLOW RATENET CAPACITY KW AT STANDAR

Pagina 20

DB-AIRE CHILLED WATER SYSTEMSBLOWER DATAMODEL DBCD/U-07DBCD/U-09DBCD/U-11DBCD/U-13DBCD/U-15DBCD/U-18DBCD/U-22DBCD/U-26DBCD-30STANDARD AIR VOLUMECMHCFM

Pagina 21

DB-AIRE CHILLED WATER SYSTEMSCHILLED WATER ELECTRICAL DATAELECTRICAL BASED ON STANDARD UNITS (WITH ELECTRIC REHEAT AND ELECTRIC HUMIDIFIER)MODELDBCD/U

Pagina 22 - CHILLED WATER DESIGN FEATURES

DB-TEMP/ DB-AIRE CHILLED WATER SYSTEMSAIR COOLED, WATER/ GLYCOL COOLED/ CHILLED WATERDIMENSIONAL DATA MODEL 2, 3, 4, 5 TON (UP FLOW) MODEL 2, 3, 4,

Pagina 23 - DB-TEMP CHILLED WATER SYSTEMS

GENERAL INFORMATIONDB-Aire units are precision environmentalcontrol systems that bring a new standard offlexibility and reliable performance to thecom

Pagina 24

DB-TEMP/ DB-AIRE CHILLED WATER SYSTEMSDIMENSIONAL DATAMODEL 7, 9, 11, 13 TON(UP FLOW)MODEL 15, 18, 22, 26 TON(UP FLOW)NOTES : 1.) MINIMUM SPACE REQUIR

Pagina 25

DB-TEMP/DB-AIRE CHILLED WATER SYSTEMSDIMENSIONAL DATAMODEL 7, 9, 11, 13 TON(DOWN FLOW)MODEL 15, 18, 22, 26 TON(DOWN FLOW)MODEL 30 TON(DOWN FLOW)NOTES

Pagina 26 - DB-AIRE CHILLED WATER SYSTEMS

REMOTE AIR-COOLED CONDENSERSTECHNICAL DATAPHYSICAL DATA ELECTRICAL DATAMODEL LENGTH 'L' FANS APPROX. MTR RPM MTR FLA (3-PHASE)QTY TOTAL L/S

Pagina 27

DRY-AIR COOLERSTECHNICAL DATAPHYSICAL DATA ELECTRICAL DATAMODEL LENGTH 'L' FANS APPROX. MTR RPM MTR FLA (3-PHASE)QTY TOTAL L/S WEIGHT 380V

Pagina 28

REMOTE HEAT EXCHANGERSCONDENSER/DRY-AIR COOLER DATACONDENSERSMODEL HEAT REJECTION THR @ 35°C(95°F) AMB 52°C(125°F) COND CONNECTION SIZE (INCH)KW/°C MB

Pagina 29 - DIMENSIONAL DATA

REMOTE HEAT EXCHANGERSDRY-AIR COOLER SELECTIONSMODEL THR FLOW RATE 35°C(95°F) 37.8°(100°F)KW MBH L/S GPM COOLER PD,KPa PD, PSI COOLER PD,KPa PD, PSIDB

Pagina 30

DB-AIREA- AIR COOLEDW- WATER COOLEDG- GLYCOL COOLEDC -CHILLED WATERD- DOWN FLOWU- UP FLOWAN- 208/230 VOLT, 3 PHASE, 60HZAR- 460 VOLT, 3 PHASE, 60HZAV-

Pagina 31

DB-AIRE MONITORING/ CONTROLThe heart of the Environmental Control Systemis the microprocessor based DB-AlarmProccessor. The liquid crystal display not

Pagina 32 - REMOTE AIR-COOLED CONDENSERS

DB-AIRE MONITORING/ CONTROLALARMSAlarm conditions are also monitored on the LCDand are enunciated by an audible alarm. Thealarm silence button will qu

Pagina 33 - DRY-AIR COOLERS

DB-AIRE MONITORING/ CONTROLDB PROCESSORCOMMUNICATION INTERFACES(Optional)Below are the available communication interfacefeatures of the DB-Alarm proce

Pagina 34 - REMOTE HEAT EXCHANGERS

DB-AIRE MONITORING/ CONTROLMetasys® is the buildingautomation system developed byJohnson Controls.Johnson itself handles theimplementation of the soft

Pagina 35 - OPTIONS AND ACCESSORIES

DB-TEMP DESIGN FEATURESDB-TEMP MODELS7-46 KW2-13 TONSAIR COOLEDWATER/GLYCOL COOLEDFRAME AND CABINETThe heliarc welded steel frame provides formaximum

Pagina 36 - DB-TEMP SERIES

DB-TEMP DESIGN FEATURESsound power level and is highly reliable. Thehigh efficiency is due to the controlled orbit withfloating seals and advanced scr