DAFC-PB Fluid Cooler
Guide Specifi cations
CABINET AND FRAME - The frame shall be constructed of 14 gauge welded tubular steel
and be coated with a heavy corrosion inhibiting fi nish for long life. The unit shall have com-
plete front and side access by means of high quality furniture grade steel doors with heavy
duty hinges. The doors shall be lined with 1” thick, 1 1/2 pound density fi berglass coated
with insulation. Each door shall be provided with sure close latches, which shall be painted
to match or contrast with the computer equipment.
COLOR - The unit shall be painted in __________________________.
BLOWER SECTIONS - The blower section shall be belt driven centrifugal type, double width,
double inlet and shall be statically and dynamically balanced at the factory as a complete as-
sembly to a maximum vibration level of two mills in any plane. The blower wheel shall be a
minimum of 15” diameter. The blower wheel shall be supported on a heavy steel shaft having
self-aligning ball bearings with a minimum life span of 100,000 hours. The blower wheel shall
be driven by a motor mounted on an adjustable slide base. The drive motor shall be 1,750
rpm. The drive package shall be belt driven with two belts and variable pitch sheave, sized
for 200% of the fan motor horsepower.
COOLING COIL - The fl uid cooler cooling coil shall be constructed of copper tubes and cor-
rugated aluminum fi ns.
E.T.L. Listing - All 60- Hz. models shall be E.T.L. listed.