Data Aire DAFC-06 Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 13
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
A
B
C
HKS, INC.
DENVER, COLORADO 80202
ARCHITECT
1900 WAZEE STREET, SUITE 209
REVISION
SHEET NO.
PLOT DATE:
© 2012 HKS, INC.
TEMPLATE VERSION:
KEY PLAN
CAVEO CONSULTING ENGINEERS, INC.
ENGLEWOOD, COLORADO 80111
MECHANICAL /
ELECTRICAL CONSULTANT
6143 WILLOW DRIVE, SUITE 405
R
A
D
I
O
L
O
G
Y
/
P
R
O
C
E
D
U
R
E
D
E
P
A
R
T
M
E
N
T
R
E
N
O
V
A
T
I
O
N
CHILDREN'S HOSPITAL COLORADO
13123 EAST 16TH AVENUE
OWNER
ANSCHUTZ MEDICAL CAMPUS
AURORA, COLORADO 80045
RIMROCK GROUP
COLORADO SPRINGS, COLORADO 80921
TECHNOLOGY CONSULTANT
1080 NEW ALLEGIANCE DRIVE, SUITE 400
STRUCTURAL CONSULTANTS, INC.
DENVER, COLORADO 80209
STRUCTURAL CONSULTANT
3400 EAST BAYAUD AVENUE, SUITE 300
HKS PROJECT NUMBER
DATE
SHEET TITLE
ISSUE
8/16/2012 4:35:05 PM
M501
2.5.0.20100809
MECHANICAL
DETAILS AND
SCHEDULES
17 AUGUST 2012
14977.004
PERMIT SET
AIR CONDITIONING UNIT SCHEDULE
Tag
Drawing
#
Service Type
Nom.
Cap.
(TONS)
Manufacturer Model
Op.
Wt.
(LBS)
Dimmensions
Mounting
Control
Type
Notes
Electric Supply Fan DX Cooling Coil
Compressor
Section
Conenser Water Chilled Water Coil Humidifier Final Filter
L
(IN)
W
(IN)
H
(IN)
V P Hz.
Single
Point
AMP/MCA/
MOP
CFM
Fan
Type
Fan
Class
E.S.P.
@ Alt.
(In.
W.C.)
Motor
HP
Total
Cap.
(M BH)
Sens.
Cap.
(MBH)
E.A.T. L.A.T
Refr.
Type
#
Comp.
FLA
(Ea)
Glygol
Type
Glycol
%
GPM
Glycol
P.D. (FT.
W.C.
Max)
Supply
Conn.
Return
Conn.
Drain
Conn.
Max.
Face
Velocity
(FPM)
Total
Cap.
(MBH)
Sens.
Cap.
(BTU
H)
E.A.T. L.A.T. Chilled H20
Supply
Conn.
Return
Conn.
H20
P.D. (In.
W.C.
Max)
Capacity
#-Steam/
Hr
Water
Type
Inlet
Size
Drain
Conn.
Size
Type Depth
MERV
Rating
DB WB DB WB DB WB DB WB GPM E.W.T.L.W.T
% of
Glycol
Type of
Glycol
AC-1 2MH1.1A ROOM A1470 CONCEALED 3 DATA-AIRE DAPC-0334 420 26.5 51 24 SPRING
ISOLATORS
INT & DDC 460 3 60 3.6/5.0/15 1200 BELT I .5 0.75 1-1/8" 1-1/8" 3/4" 400 27300 24100 75.0
°F
61.0 °F 52.5 °F 51.2 °F 11 45.0 °F 50.3 °F 0 NA 1 1/8" 1 1/8" 9.70 5 DCW 1/4" 3/4" PLEATED 2' - 0" 8
AC-2 2MH1.1A ROOM A1408 CONCEALED 5 DATA-AIRE DAPC-534 530 36 51 24 SPRING
ISOLATORS
INT & DDC 460 3 60 4.5/5.6/15 2500 BELT I .5 1.5 1-1/8" 1-1/8" 3/4" 500 57600 52200 75.0
°F
61.0 °F 53.9 °F 52.0 °F 17 45.0 °F 51.0 °F 0 NA 1 1/8" 1 1/8" 20.80 5 DCW 1/4" 3/4" PLEATED 2' - 0" 8
AC-3 2MH1.1A ROOM A1477 CONCEALED 5 DATA-AIRE DAPC-534 530 36 51 24 SPRING
ISOLATORS
INT & DDC 460 3 60 4.5/5.6/15 2500 BELT I .5 1.5 1-1/8" 1-1/8" 3/4" 500 57600 52200 75.0
°F
61.0 °F 53.9 °F 52.0 °F 17 45.0 °F 51.0 °F 0 NA 1 1/8" 1 1/8" 20.80 5 DCW 1/4" 3/4" PLEATED 2' - 0" 8
AC-4 1MH1.1C C1277 CONCEALED 5 DATA-AIRE DAPG-0534P 885 54 51 24 SPRING
ISOLATORS
INT & DDC 208 3 60 25.3/30.4/50 2000 BELT I .5 1.5 48900 41400 75 °F 61 °F 52 °F 50 °F R-410A 1 9.6 PROPYLENE 40 17.5 15 1-1/8" 1-1/8" 3/4" PLEATED 2' - 0" 8
AC-5 1MH1.1C C1277 CONCEALED 5 DATA-AIRE DAPG-0534P 885 54 51 24 SPRING
ISOLATORS
INT & DDC 208 3 60 25.3/30.4/50 2000 BELT I .5 1.5 48900 41400 75 °F 61 °F 52 °F 50 °F R-410A 1 9.6 PROPYLENE 40 17.5 15 1-18/" 1-1/8" 3/4" PLEATED 2' - 0" 8
NOTES:
1. ABOVE CEILING UNIT WITH DUCTED SUPPLY, PLENUM RETURN.
2. PROVIDE MINI DAP-III CONTROLLER WITH BACNET INTERFACE.
3. NO REHEAT.
4. FACTORY PROVIDED DISCONNECT.
5. FACTORY PROVIDED CONDENSATE PUMP.
6. MICRO-SWTICH FOR CONDENSATE PAN OVERFLOW.
7. STAINLESS STEEL DRAIN PAN.
FAN SCHEDULE
Tag
Drawing
Number
Area
Served
Type
Manufactur
er
Model
Operating
Weight
Dimmensions
Controls Notes
Fan
L W H CFM Fan Type Drive
T.S.P. @
Alt. (In.
W.C.)
RPM Max
Motor Sound
HP V-P Motor Type Starter E-Power
Sound
Inlet (LwA)
Sound
Outlet
(LwA)
EF-201 A&B 10TH FLOOR HOT LAB INDUSTRIAL COOK 70-MHA-SD 275 18 27 30 DDC 1,2,3,4 800 CFM INDUSTRIAL
UTILITY
BELT 4.0 2841 1.5 460-3 ODP VFD YES 88 78
EF-202 2MH1.1A MRI-3&4 INLINE COOK 195R8B 420 21 27 44 DDC 3600 CFM UPBLAST BELT 1.0 1379 1.5 460-3 ODP VFD YES -- 78
NOTES:
1. MOUNT ON EXISTING INERTIA BASES IN 10TH FLOOR MECHANICAL ROOM.
2. CONNECT TO DUCTWORK WITH FLEXIBLE CONNECTORS.
3. EXTENDED LUBE LINES.
4. BELT GAURD.
5. ADJUSTABLE SUPPORTS.
FLUID COOLER UNIT
Tag Service
Manufactur
er
Model
Operating
Weight
(LBS)
Dimmensions
Controls Comments
Electric Condenser Pump
L W H Voltage Phase Hz.
# of
Condenser
Fans
Fan HP
(ea)
FLA (ea) # of Pumps HP (ea) FLA (ea) GPM
Total Head
(FT.)
FCU-1 RADING ROOM AC
UNITS
DATA AIRE DAFC-2834 970 120 49 40 INT + DDC 1-4 208 60 Hz 3 .75 4.6 2 2 6.0 35 90
NOTES:
1. SINGLE POINT ELECTRICAL CONNECTION WITH FACTORY DISCONNECT.
2. REDUNDANT PUMPS WITH AUTO CHANGEOVER.
3. FACTORY PROVIDED EXPANSION TANK.
4. SYSTEM TO BE FILLED WITH 40% P.G.
AIR TERMINAL BOX SCHEDULE
Tag Type
Cooling Air Quantity
Heating
Air CFM
Heating Coil
Inlet
Size
Manufacturer Model # Notes ControlsMax. CFM Min. CFM
E.A.T.
F)
L.A.T.
F)
BTUH
Flow
(GPM)
Pipe
Size
E.W.T.
F)
L.W.T.
F)
S1D REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S2D REHEAT 1950 CFM 475 CFM 55 100 5.3 180 150 14" EXISTING
S3B REHEAT 700 CFM 150 CFM 55 100 1.9 180 150 8" EXISTING
S3D REHEAT 1950 CFM 475 CFM 55 100 5.3 180 150 14" EXISTING
S4D REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S6B REHEAT 400 CFM 75 CFM 55 100 1.1 180 150 6" EXISTING
S7B REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S8B REHEAT 400 CFM 75 CFM 55 100 1.1 180 150 8" EXISTING
S9B REHEAT 1000 CFM 250 CFM 55 100 2.7 180 150 10" EXISTING
S10B REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S11B REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S16B REHEAT 1430 CFM 400 CFM 55 100 4.1 180 150 12" EXISTING
S21B REHEAT 700 CFM 150 CFM 55 100 1.9 180 150 8" EXISTING
S23B REHEAT 1500 CFM 350 CFM 55 100 4.1 180 150 12" EXISTING
S32A REHEAT 1950 CFM 475 CFM 55 100 5.3 180 150 14" EXISTING
S34C REHEAT 700 CFM 150 CFM 55 100 1.9 180 150 8" EXISTING
S39A REHEAT 1950 CFM 475 CFM 55 100 5.3 180 150 14" EXISTING
S40A REHEAT 1950 CFM 475 CFM 55 100 5.3 180 150 12" EXISTING
VAV-1 REHEAT 570 CFM 100 CFM 100 55 100 4730 .3 3/4" 180 150 8" TITUS DESV-8 DDC
VAV-2 REHEAT 1060 CFM 530 CFM 530 55 100 25040 1.7 3/4" 180 150 10" TITUS DESV-10 DDC
VAV-3 REHEAT 95 CFM 50 CFM 50 55 100 2360 .2 3/4" 180 150 6" TITUS DESV-6 DDC
VAV-4 REHEAT 2575 CFM 1290 CFM 1290 55 100 60950 4.1 1" 180 150 10" TITUS DESV-10 DDC
VAV-6 REHEAT 300 CFM 300 CFM 300 55 100 14180 0.9 3/4" 180 150 6" TITUS DESV-6 DDC
VAV-7 REHEAT 800 CFM 400 CFM 400 55 100 18900 1.3 3/4" 180 150 10" TITUS DESV-10 DDC
VAV-8 CONSTANT
VOLUME
280 CFM 280 CFM 280 55 100 13230 0.9 3/4" 180 150 6" TITUS DESV-6 DDC
NO. DESCRIPTION DATE
3
CEILING DEVICE SCHEDULE
Mark Manufacturer Model #
Module
Size
Neck
Size
Max
N.C.
Notes
EG-1 TITUS 23RL 18x10 18x10 <30
ER-1 TITUS PAR 12x12 6x6 <30
RR-1 TITUS PAR 24x24 6x6 <30
RR-2 TITUS PAR 24x24 8x8 <30
RR-3 TITUS PAR 24x24 10x10 <30
RR-4 TITUS PAR 24x24 12x12 <30
SD-1 TITUS TMS 24x24 6"Ø <30
SD-2 TITUS TMS 24x24 8"Ø <30
SD-3 TITUS TMS 24x24 10"Ø <30