PROJECT: TCH RADIOLOGY AND PROCEDURE CENTER PHASE I
LOCATION: AURORA, CO
DATE: 1/21/2013
CONTACT: Trevor Quain
Air Handling Unit
AUTHOR: Greg Barnes
Test Date: January 20, 2013
SYSTEM/UNIT: AC-4-02
AREA:
Tested By: Greg Barnes
Unit Data
Unit Manufacturer
DATA AIRE
Unit Model Number
DAPG-0532-P
Unit Serial Number
2012-3185-B
Total CFM Design
2000 CFM
Test Data
Total CFM Actual
2005
Return Air CFM Actual
2005
AC-4-02 / Supply Fan
Fan RPM Actual
1045
Motor Volts 1
208
Motor Volts 2
209
Motor Volts 3
210
Motor Amps 1
2.5
Motor Amps 2
2.4
Motor Amps 3
2.6
Motor Data
AC-4-02 / Supply Fan
Motor Manufacturer
LESSON
Motor HP
1-1\2
Motor RPM
1750
Motor Frame
145T
Motor Rated Volts
200-230/460
Motor Phase
3
Motor FL Amps
5.2-5.4\2.7
Motor Service Factor
1.15
Sheave Data
AC-4-02 / Supply Fan
Motor Sheave Model
1VP56
Motor Sheave Bore
7\8 in.
Fan Sheave Model
1AK6.75 OD
Fan Sheave Bore
3/4 in.
Number of Belts
1
Belt Size
A42
Test Pressures
Filter SP In
ATMOSPHERE in. wc
Filter SP Out
NO ACCESS in. wc
Cool. Coil SP In
NO ACCESS in. wc
Cool. Coil SP Out
0.51 in. wc
Fan SP In
0.51 in. wc
Fan SP Out
0.05 in. wc
AC-4-02 Supply Outlet Summary
% Final
Deviati
Final
Reading
%
Prelim
Prelim
Reading
Design
Readin
AK
Factor
Face
Area
Type of
Readin
Outlet
Type
System / Unit
Outlet-01
96385410 103400
Outlet-02
100400615 154400
Outlet-03
105420595 149400
Outlet-04
101405545 136400
Outlet-05
99395635 159400
------
2,000 2,800 2,005
Totals :
140 % 100 %
* Notes
JEDI
JEDI Balancing, Inc.