PROJECT: TCH RADIOLOGY AND PROCEDURE CENTER PHASE I
LOCATION: AURORA, CO
DATE: 1/21/2013
CONTACT: Trevor Quain
Air Handling Unit
AUTHOR: Greg Barnes
Test Date: January 20, 2013
SYSTEM/UNIT: E-AHU-01
AREA:
Tested By: Greg Barnes
* Notes
Test Date: January 17, 2013
SYSTEM/UNIT: E-AHU-01 / FPB-122
AREA:
Tested By: Greg Barnes
Unit Data
VAV Address
169
Box Inlet Size
0.52
K Factor
2.15
Test Data
Max Design CFM
800 CFM
Max Actual CFM
795 CFM
Min Design CFM
240 CFM
Min Actual CFM
245 CFM
Reheat Design CFM
800 CFM
Reheat Actual CFM
810 CFM
E-AHU-01 / FPB-122 Supply Outlet Summary
% Final
Deviati
Final
Reading
%
Prelim
Prelim
Reading
Design
Readin
AK
Factor
Face
Area
Type of
Readin
Outlet
Type
System / Unit
SD
Outlet-01
98195210 105200
SD
Outlet-02
100200190 95200
SD
Outlet-03
98195165 83200
SD
Outlet-04
103205190 95200
------
800 755 795
Totals :
94 % 99 %
* Notes
JEDI
JEDI Balancing, Inc.