
PROJECT: TCH RADIOLOGY AND PROCEDURE CENTER PHASE I
LOCATION: AURORA, CO
DATE: 1/21/2013
CONTACT: Trevor Quain
Air Handling Unit
AUTHOR: Greg Barnes
Test Date: January 17, 2013
SYSTEM/UNIT: E-AHU-01 / VAV-121
AREA:
Tested By: Greg Barnes
Unit Data
VAV Address
141
Box Inlet Size
0.52
K Factor
1.98
Test Data
Max Design CFM
600 CFM
Max Actual CFM
592 CFM
Min Design CFM
180 CFM
Min Actual CFM
185 CFM
E-AHU-01 / VAV-121 Supply Outlet Summary
% Final
Deviati
Final
Reading
%
Prelim
Prelim
Reading
Design
Readin
AK
Factor
Face
Area
Type of
Readin
Outlet
Type
System / Unit
SD
Outlet-01
48240210 84250
SD
Outlet-02
2705260 12050
SD
Outlet-03
145165 110150
SD
Outlet-04
103155165 110150
------
600 600 592
Totals :
100 % 99 %
Comentarios a estos manuales