Energy Saver Coil - The Data Aire Energy Saver Coil is built
into the system to provide total required capacity. Whenever
the incoming water/glycol temperature is below 45° F/7.2° C,
Energy Saver cooling is available. Energy Saver mode oper-
ates in the following range: Return air setpoint plus deadband
plus two degrees. The Energy Saver will operate providing
there is a need for cooling. The valve will open at setpoint
plus deadband. The valve will modulate as long as the space
is between setpoint plus deadband plus 2 degrees. If the tem-
perature falls below the deadband minus setpoint, the valve
will close and the space is considered satis ed. While still in
Energy Saver with the valve modulating, if the temperature
goes beyond setpoint plus deadband plus 2 degrees the Energy
Saver valve will close and DX cooling will begin.
The Energy Saver Coil includes a 3-way pressure control
valve on condenser water circuit, and a 3-way valve on the
Energy Saver coil. Common piping for coil and condenser is
provided.
Energy Saver/Compressor Supplement - Units with the En-
ergy Saver Coil can be provided with compressor supplement
if the Energy Saver is not suf cient as a stand alone system.
When the incoming water/glycol temperature is below the
setpoint of the water changeover thermostat, the Energy Saver
mode is enabled (even if there is no call for cooling). Upon a
call for cooling (setpoint plus deadband), the valve will open
proportionally - 10% for each 0.1° above setpoint plus dead-
band. The compressor will come on at setpoint plus deadband
plus 1.0° (the valve is 100% open at this point). The compres-
sor will go off at setpoint plus deadband plus 0.7°. The valve
will close proportionally - 10% for each 0.1° below setpoint
plus deadband. An air discharge sensor is factory installed.
Auxiliary Chilled Water Coil - Where an existing chilled
water loop is available, units can be tted with an auxiliary
chilled water coil. Units will operate using the chilled water
for cooling. Upon a loss of water ow or an increase in room
temperature the system will bring on compressor (DX) cool-
ing. Separate piping is provided for the chilled water coil and
refrigeration connections.
Auxiliary Chilled Water Coil/Compressor Supplement - The
Auxiliary Chilled Water Coil can be provided with compressor
supplement for extended savings by allowing the compressor
to supplement operation as needed when the chilled water is
not suf cient on a stand alone basis. An discharge air sensor is
factory installed. (See Energy Saver/Compressor Supplement
for details).
OPTIONS
Remote Temperature and Humidity Sensors - Temperature and
humidity sensors may be ordered for remote wall mounting in
lieu of the standard return air sensors. Sensors are provided in
a wall mounted plastic case for remote sensing of temperature
and humidity. 25 feet of shielded cable is provided for eld
wiring.
Smoke Detector - A unit mounted smoke detector will shut
down the unit if smoke is sensed. The microprocessor will
sound an alarm and display a “SMOKE DETECTED” message.
The smoke detector is mounted in the return air stream and is
provided with auxiliary contacts.
Next Size Larger Motor - Should your installation require addi-
tional air ow or increased static pressure you can order a larger
motor to meet these requirements.
Hot Water Reheat - Where hot water is available, a unit in-
stalled reheat coil can use hot water reheat. The coil is designed
for 150 psi maximum water pressure and includes a 2-way valve
(a 3-way valve is optional).
Hot Gas Reheat - Unit hot gas discharge is used for reheat and
maximum system ef ciency.
(Note: Units with Hot Gas Bypass option are not available with
hot gas reheat).
Steam Reheat - When your building already has steam lines this
option may be a more bene cial way of providing reheat to your
unit. When selected the unit comes with a steam coil and 2-way
valve, replacing the standard electric reheat.
Compressor Rotalock Valves - These valves facilitate servicing
and permit the changing of compressor without the complete
loss of refrigerant.
Unit Mounted Disconnect - A unit mounted nonautomatic dis-
connect switch is installed in the high voltage electrical section.
The operating mechanism allows access to the high voltage
electrical components when switched to the “OFF” position.
The operating mechanism (handle) protrudes through the deco-
rative door.
Hot Gas Bypass - Hot gas bypass may be ordered for changing
load conditions. The hot gas bypass is installed between the
compressor discharge line and the leaving side of the expan-
sion valve through a side outlet distributor. The system with