AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unit
MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
CONDENSING UNIT
Condensing unit at 95° F ambient DRCU-03 DRCU-03 DRCU-05 DRCU-05 DRCU-09 DRCU-11 DRCU-15
208-230/3/60 FLA/MCA/MOP 15/18/30 18/21/35 22/27/45 25/30/60 35/42/80 43/51/90 61/73/150
460/3/60 FLA/MCA/MOP 6.8/7.9/15 8.4/9.9/20 12/14/25 12/14/25 19/23/45 23/27/50 28/34/60
Condensing unit at 100° F ambient DRCU-03 DRCU-03 DRCU-05 DRCU-06 DRCU-11 DRCU-15 DRCU-17
208-230/3/60 FLA/MCA/MOP 15/18/30 18/21/35 22/27/45 25/30/60 39/47/80 43/51/90 61/73/150
460/3/60 FLA/MCA/MOP 6.8/7.9/15 8.4/9.9/20 12/14/25 12/14/25 21/26/45 23/27/50 28/34/60
Condensing unit at 105° F ambient DRCU-03 DRCU-05 DRCU-06 DRCU-07 DRCU-15 DRCU-17 DRCU-21
208-230/3/60 FLA/MCA/MOP 15/18/30 18/21/35 22/27/45 25/30/60 39/47/80 43/51/90 65/78/150
460/3/60 FLA/MCA/MOP 6.8/7.9/15 8.4/9.9/20 12/14/25 12/14/25 21/26/45 23/27/50 30/36/90
Notes: Condensing units are not available in 575 volts.
Condensing units are selected at sea level.
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.