MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
CAPACITY in kW/hr - gross
80° DB/67° WB Total 26,700 39,700 53,900 62,500 N/A N/A N/A
50% RH Sensible 20,100 29,700 40,900 49,600 N/A N/A N/A
75° DB/62.5° WB Total 24,600 36,900 49,700 58,200 N/A N/A N/A
50% RH Sensible 19,300 28,700 39,200 47,800 N/A N/A N/A
75° DB/61° WB Total 24,000 35,800 48,500 56,600 N/A N/A N/A
45% RH Sensible 20,700 30,600 42,100 51,200 N/A N/A N/A
72° DB/60° WB Total 23,400 35,300 47,200 55,700 N/A N/A N/A
50% RH Sensible 18,800 28,100 38,300 46,800 N/A N/A N/A
72° DB/58.6° WB Total 22,700 34,300 46,300 54,400 N/A N/A N/A
45% RH Sensible 19,900 29,700 40,800 49,800 N/A N/A N/A
FAN SECTION
Airfl ow - CFM 800 1,200 1,600 2,000 - - -
Number of fans 1 1 1 1 - - -
Standard fax - diameter (mm) 450 450 450 450 - - -
Fan motor - kW/HP 1/1.4 1/1.4 1/1.4 1/1.4 - - -
External static pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 - - -
Maximum E.S.P. 1.5 1.5 1.5 1.3 - - -
Next size fan - diameter (mm) N/A N/A N/A 500 - - -
Fan motor - kW/HP - - - 2.8/3.7 - - -
Minimum E.S.P. - - - 1.5
COMPRESSORS
Type Scroll Scroll Scroll Scroll - - -
Quantity 1 1 1 1 - - -
Refrigerant R-410A R-410A R-410A R-410A - - -
EVAPORATOR COIL
Face area - sq ft 4.2 4.2 6.25 6.25 - - -
Rows of coils 3 3 4 4 - - -
Face velocity - fpm 190 286 256 320 - - -
REHEAT SECTION
Electric Standard Standard Standard Standard - - -
kW 6 6 12 12 - - -
Capacity - Btu/hr 20,490 20,490 40,980 40,980 - - -
HUMIDIFIER SECTION
Steam generator Standard Standard Standard Standard - - -
kW 3.4 3.4 3.4 3.4 - - -
Capacity - lb/hr 10 10 10 10 - - -
AIR COOLED: Performance data at STANDARD AIRFLOW with remote air cooled condenser
R-410A
gForce GT also available in R-407C. Data in a separate brochure.