Data Aire DAFC-11 Especificaciones Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
20
R-407C
MODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13
ELECTRICAL SECTION Standard Motor
Electrical data based on: electric reheat - YES, steam generator humidi er YES, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 77/94/110 88/108/125 100/123/150
460/3/60 FLA/MCA/MOP 37/45/50 40/50/60 46/56/70
575/3/60 FLA/MCA/MOP 28/35/40 31/38/45 38/46/60
Electrical data base on: electric reheat - NO, steam generator humidi er - YES, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 51/63/80 63/76/100 75/91/125
460/3/60 FLA/MCA/MOP 25/31/40 29/35/50 34/42/60
575/3/60 FLA/MCA/MOP 19/23/30 22/26/35 28/35/50
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 77/94/110 88/108/125 100/123/150
460/3/60 FLA/MCA/MOP 37/45/50 40/50/60 46/56/70
575/3/60 FLA/MCA/MOP 28/35/40 31/38/45 38/46/60
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 35/42/70 46/56/90 58/71/110
460/3/60 FLA/MCA/MOP 18/22/35 22/26/40 27/32/50
575/3/60 FLA/MCA/MOP 13/16/25 16/19/30 23/27/45
 STANDARD MOTOR
Motor horsepower 2 3 3
208-230/3/60 FLA 6.2 9.0 9.0
460/3/60 FLA 3.1 4.4 4.24
575/3/60 FLA 2.5 3.3 3.3
COMPRESSOR
208-230/3/60 FLA 28.8 37.2 49.4
460/3/60 FLA 14.7 17.2 22.4
575/3/60 FLA 10.8 12.4 19.2
* - W for water or G for glycol
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
WATER/GLYCOL COOLED: Performance data at STANDARD air ow
Vista de pagina 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 43 44

Comentarios a estos manuales

Sin comentarios