
6
PRECISION COOLING
Modular Data Temp Series units are precision environmental
control systems that bring a standard of reliable performance
to today’s demanding market. Small to large data centers,
telecommunication sites, or where access and/or fl oor space
is limited, Modular Data Temp units can meet these demands.
Modular Data Temp process cooling systems are available in
8, 10, and 13 nominal ton capacities with upfl ow or downfl ow
air distribution in air cooled or water/glycol cooled direct ex-
pansion models. Each Modular Data Temp unit is factory run
tested and put through a vigorous quality control procedure.
COMFORT
Computer rooms, telecommunication switch sites, and other
environmentally controlled spaces require air which is clean
and properly distributed, with precisely controlled temperature
and humidity. Building or “people comfort” systems are not
designed to meet these demands. Modular Data Temp systems
are designed to satisfy these goals.
DESIGN
Modular Data Temp systems feature a specially designed
compact tubular steel frame which minimizes the space re-
quirement of air conditioning equipment in the controlled area.
Although compact, all parts are easily accessible providing ex-
cellent serviceability. Units are fi nished with a furniture-grade
insulated steel cabinet painted in your choice of color.
CONTROL
The heart of the Modular Data Temp system is the Data Alarm
Processor-III (DAP-III), a microprocessor based controller
designed for precision environmental control. The DAP-III
not only controls and monitors temperature, humidity, airfl ow,
and cleanliness, it provides component runtimes, alarm history,
and automatic self-tests. All information is provided on a 2
row, 80 character, backlit liquid crystal display.
DATA AIRE DELIVERS
Engineered for high performance and reliability, each Modular
Data Temp unit comes with Data Aire’s commitment to excel-
lence. This commitment began with Data Aire’s fi rst process
cooling unit and has continued for more than 40 years of build-
ing the industry’s fi nest precision control equipment. Standard
ship cycle is 30 days from date of order. With the optional
premium “quick ship” program, units can be expedited to ship
in as little as one week. All units are built to your specifi c
order. Call your nearest Data Aire representative for more
information.
FRAME/CABINET
The heliarc welded tubular steel frame provides for maximum
strength and ease of access with minimum space requirement.
Side and front panels can be easily opened and removed with
quarter-turn fasteners, allowing full access to all unit compo-
nents. All panels include 1 inch thick, 1-1/2 pound density
insulation for protection and sound attenuation. All parts are
easily accessible.
COIL SECTION
Designed for draw through application, the computer selected
coil offers greater effi ciency in the cooling and dehumidifi ca-
tion process. Air bypass is provided to prevent saturated air
from being introduced into the controlled space. The coil sec-
tion is provided with a stainless steel drain pan.
FAN SECTION
The centrifugal, forward curved, double width, double inlet
blower confi guration is engineered for quiet reliable operation.
The belt driven variable pitch drive provides adjustable air
fl ow capability to match load requirements of the controlled
space. The draw through design insures even air distribution
across the coil, low internal cabinet losses, and static sealing
of the fi lter section. Motors are mounted on an adjustable slide
base and have internal overload protection.
Data Aire, Inc.
Modular Data Temp
Comentarios a estos manuales