FILTER SECTION
Units are provided with 4 inch deep, 30% ef cient lters (based
on ASHRAE Std. 52.1-92). The lter section is accessible from
the top or side on down ow units and the right hand side on
up ow units.
REHEAT
Three stage electric reheat is standard. Low-watt density nned
tubular sheathed coils are constructed of stainless steel and
provide ample capacity to maintain room dry bulb conditions
during dehumidi cation. Low-watt density coils eliminate ion-
ization associated with open air electric resistance heating.
HUMIDIFICATION
Modular Data Temp units include an electric steam genera-
tor humidi er with a “quick change” disposable cylinder and
an auto- ush cycle. The steam generator humidi er with its
patented control system optimizes cylinder life and energy ef-
ciency by concentrating incoming water to a predetermined
conductivity much higher than that of the entering water.
The control system continuously monitors the conductivity in
the cylinder through its electronics which allows water to be
ushed as often as is necessary to maintain the capacity at this
design conductivity. The high design conductivity results in a
minimum ushing of heated water, thereby saving energy. The
humidi er is designed to allow units at any voltage to produce
full rated steam output capacity at an optimum water level
based on the design conductivity.
REFRIGERATION CIRCUIT
The single circuit, refrigeration circuit is designed around a
high ef ciency hermetic scroll compressor. These durable,
heavy duty, fully welded compressors have no gaskets or seals,
substantially reducing the possibility of refrigerant or oil leak-
ing into the controlled space or environment. Scroll compres-
sors bring a combination of reliability, ef ciency and improved
system sound performance to the Modular Data Temp line.
The refrigeration circuit includes built-in compressor overload
protection, crankcase heater, lter drier, sight-glass, adjustable
expansion valve with external equalizer, low pressure override
timer (air cooled units), manual reset high pressure control,
compressor short cycle timer, and rotolock service valves.
Water/glycol cooled units include a counter ow plate- n
condenser sized to provide the required heat of rejection with
minimum water/glycol ow for a low total pressure drop.
Head pressure water regulating valves control the condenser
water ow to maintain proper head pressure under varying load
conditions.
Air Cooled with Remote Outdoor Condenser - A wide range
of outdoor condensers are available. Condensers are manu-
factured by Data Aire and sized to meet the heat rejection and
ambient conditions as required. The industrial duty design
includes aluminum corrosion resistant housing, aluminum
nned copper tube coils, powder coated fan guards, energy
ef cient thermally protected direct drive motors and variable
fan speed control on lead fan motor for proper control down
to -20° F. Additional fan motors are controlled with ambient
thermostats.
Air Cooled with Indoor Condenser - A wide range of oor
mounted indoor condensers with horizontal intake and dis-
charge are available for applications where an outdoor con-
denser cannot be used. Finished to match the indoor evapo-
rator section, the condenser includes a centrifugal, forward
curved, double width, double inlet blower engineered for
quiet, reliable operation. The belt driven variable pitch drive
provides adjustable air ow. The motor has internal over-
load protection and is mounted on an adjustable slide base.
Indoor condensers are provided with a factory mounted and
piped receiver, complete with a head pressure control valve
to maintain head pressure under varying ambient conditions
down to -30° F.
Air Cooled with Outdoor Condensing Unit - When compres-
sors are required to be out of the controlled space, Modular
Data Temp units are available with a remote outdoor con-
densing unit. The condensing unit includes a hermetic
scroll compressor with built-in overload protection, crankcase
heater, lter drier, sight-glass and condenser coil. The coil is
constructed with copper tubes and aluminum ns. The hous-
ing is corrosion resistant aluminum with vertical air discharge.
The condenser fan is a variable speed type for head pressure
control down to -20° F ambient temperature. Additional fan
motors are controlled by ambient fan thermostats.
Water/Glycol Cooled with Remote Outdoor Fluid Cooler
- Remote outdoor uid coolers are available in a variety of
sizes. Each uid cooler includes aluminum corrosion resistant
housing, aluminum nned copper tube coil, coated fan guards,
surge tank, motor contactor, pump contactor and energy ef-
cient thermally protected direct drive motors. Multiple fan
motors are staged to maintain the desired condenser supply
uid temperature.
Design Features