Data Aire DAFC-11 Especificaciones Pagina 25

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 24
25 R-407C
WATER/GLYCOL COOLED: Performance data at OPTIONAL air ow
MODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13
ELECTRICAL SECTION Next Size Motor
Electrical data based on: electric reheat-YES, steam generator humidi er-YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 85/103/110 102/122/125 114/137/175
460/3/60 FLA/MCA/MOP 40/49/50 47/56/60 52/63/80
575/3/60 FLA/MCA/MOP 31/38/45 36/43/50 43/51/60
Electrical data based on: electric reheat-NO, steam generator humidi er-YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 60/71/90 77/90/110 89/105/150
460/3/60 FLA/MCA/MOP 29/34/45 36/42/50 41/48/60
575/3/60 FLA/MCA/MOP 22/26/35 27/32/40 34/40/50
Electrical data based on: electric reheat-YES, steam generator humidi er-NO, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 85/103/110 102/122/125 114/137/175
460/3/60 FLA/MCA/MOP 40/49/50 47/56/60 52/63/80
575/3/60 FLA/MCA/MOP 31/38/45 36/43/50 43/51/60
Electrical data based on: electric reheat-NO, steam generator humidi er-NO, and NEXT SIZE MOTOR.
230/3/60 FLA/MCA/MOP 43/51/70 60/70/100 72/85/125
460/3/60 FLA/MCA/MOP 21/25/40 28/33/50 33/39/60
575/3/60 FLA/MCA/MOP 16/19/30 21/24/35 28/33/50
 NEXT SIZE MOTOR
Motor horsepower 5 7.5 7.5
230/3/60 FLA 15.0 23.0 23.0
460/3/60 FLA 6.6 11.0 11.0
575/3/60 FLA 5.3 8.6 8.6
OUTDOOR DRY COOLER
Dry coolers are selected at sea level. Refer to page 30 for dry cooler electrical data.
Dry cooler selection at 95° F ambient DAFC-15 DAFC-21 DAFC-21
Dry cooler selection at 100° F ambient DAFC-21 DAFC-24 DAFC-30
* - W for water or G for glycol
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps