Data Aire DAFC-11 Manual de instalación Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
11
2.1.3 Suction Lines
Some applications call for the compressor to be mounted as part of the condenser, more commonly
referred to as a condensing unit. Such require eld piping of liquid and suction lines. Suction lines
are trapped similarly to discharge lines. Common practice for suction line selection and installation
should be followed. Suction lines should always be insulated.
2.1.4 Connection Sizes, Air Cooled Units
MODEL HOT GAS LINE LIQUID LINE SUCTION LINE
DTAD/U-02 1/2” 1/2” 3/4”
DTAD/U-03 1/2” 1/2” 3/4”
DTAD/U-04 1/2” 1/2” 3/4”
DTAD/U-05 1/2” 1/2” 3/4”
DTAD/U-08 3/4” 5/8” 1-3/8”
DTAD/U-10 3/4” 5/8” 1-3/8”
DTAD/U-13 3/4” 5/8” 1-3/8”
Note: Units will have a liquid line and either a hot gas or suction line
Field connections at the indoor evaporator and remote condenser or condensing unit will
not necessarily be the same as the eld pipe size required. In some cases these sizes
will vary signi cantly.
2.1.5 Field Piping, Remote Condenser
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 35 36

Comentarios a estos manuales

Sin comentarios