4.5.3 Low Pressure Cutout Switch
Each circuit includes a low pressure cutout switch with automatic reset. The switch is located near
the compressor section.
The pressure rating for R-407C systems is 30 PSIG, cut in at 50 PSIG.
The pressure rating for R-410A systems is 34 PSIG, cut in at 68 PSIG.