Data Aire DAFC-11 Manual de instalación Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
17
the control panel). The control circuit is 24 VAC and the eld provided contact or switch should have
a minimum rating of 10 amps.
The remote shutdown contacts are always terminals #1 and #2 on the terminal block designated
TB2. The unit will ship with a factory wired metal jumper clip (bridge) that connects terminal #1 to
terminal #2. Remove the clip prior to installing the eld wires.
3.7 Remote Alarm Contacts
The unit’s controller (DAP-III) provides a remote alarm output contact that can be eld addressed on
terminals #11 and #13 of terminal block TB2. This is a normally open, close on alarm, dry contact,
intended to be used in a control circuit not exceeding 5 amps at 24 VAC.
This programmable output contact will close on a failure and remain closed until the alarm is no
longer present. Three additional alarms contacts come with the optional relay module. The terminal
designations for these alarms output contact pairs are #40 and #42, #43 and #45, and #48 and #50.
3.8 Remote Sensors
Remote sensors are optional. Although existing unit mounted sensors can be removed for remote
mounting, the remote sensor option provides a more convenient means of eld installation. The
standard unit sensors have a predetermined length of cable and are mounted in a remote sensor
enclosure. The temperature and humidity sensors require a total of six (6) wires and should be
twisted, shielded cable type.
3.9 Condensate Pumps
Condensate pumps that ship loose normally require a separate source of 110 volt power. Always
check the pump power requirements before connecting power. Condensate pumps are available
in other voltages.
Condensate pumps may also come mounted and powered. While no outside power source is re-
quired, eld piping is still a requirement.
Condensate pumps are wired to display a “HIGH CONDENSATE WATER LEVEL” alarm. The wir-
ing for this alarm message must be done in the eld on pumps that ship loose. Factory mounted
pumps come pre-wired.
3.10 Condensate Probe
A condensate probe for sensing under oor water is included with this unit. The probe is in a plastic
bag with 15 feet of coiled wire. The probe is a at plate that is typically placed below the unit in a
location where water is likely to accumulate.
Place the probe at on the oor on top of a thin layer of non-conductive silicone. Secure the at-
tached wires where necessary. A longer length of wire may be used if required.
NOTE: failure to uncoil the wire attached to the condensate probe can result in a nuisance
alarm (water detected). If the probe is not going to be used it should be disconnected.
3.11 Water Sensing Cable
Another option for water sensing is the Water Detection Cable. This is a long cable that can sense
moisture anywhere along its length. It is typically placed below the unit in a rectangular pattern that
matches the perimeter of the unit.
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 35 36

Comentarios a estos manuales

Sin comentarios