5.0 GLYCOL SYSTEMS
5.1 Glycol Concentration
The system must be lled with water and the appropriate amount of ethylene or propylene glycol
to protect against winter freezing. To achieve the approximate glycol concentration, it is necessary
to know the total system volume. The total system volume consists of the uid cooler volume, the
evaporator unit volume and the volume of the inter-connecting piping.
The following tables can be used for arriving at an approximate system volume. After installation,
the glycol percentage should be checked. The glycol percentage should be checked at regular in-
tervals to ensure against freeze protection.
5.1.1 Internal (Fluid) Volume – Down ow Units
Volume (gallons) - no Volume (gallons) – with
Evaporator Model Energy Saver Coil Energy Saver Coil
DT*D-02 2.0 3.5
DT*D-03 2.5 3.5
DT*D-04 2.5 5.0
DT*D-05 2.5 5.0
DT*D-08 4.5 N/A
DT*D-10 5.0 N/A
DT*D-13 5.5 N/A
*W = Water Cooled G = Glycol Cooled
5.1.2 Internal (Fluid) Volume – Up ow Units
Volume (gallons) - no Volume (gallons) – with
Evaporator Model Energy Saver Coil Energy Saver Coil
DT*U-02 1.6 3.0
DT*U-03 1.6 3.0
DT*U-04 2.0 4.5
DT*U-05 2.0 4.5
DT*U-08 4.5 N/A
DT*U-10 5.0 N/A
DT*U-13 5.5 N/A
*W = Water Cooled G = Glycol Cooled