NOTE: Charging to a full liquid line sight-glass should never be the sole means of de-
termining the correct refrigerant charge. Other parameters such as superheat, suction
pressure, head pressure, sub-cooling and ambient temperature are also important. A
system charged to a clear sight-glass is often overcharged.
4.3.2 Factory Charge for Water/Glycol Cooled Systems
Evaporator Model R-407C R-410A
DT*D/U-02 Consult Factory Consult Factory
DT*D/U-03 Consult Factory Consult Factory
DT*D/U-04 Consult Factory Consult Factory
DT*D/U-05 Consult Factory Consult Factory
DT*D/U-08 Consult Factory Consult Factory
DT*D/U-10 Consult Factory Consult Factory
DT*D/U-13 Consult Factory Consult Factory
*W = Water Cooled G = Glycol Cooled
4.4 Refrigerant Handling
The use of recovery/recycling is required by the US Environmental Protection Agency (EPA) regu-
lations. Technicians who service and dispose of air conditioning and refrigeration equipment must
recover the refrigerant instead of venting to the atmosphere.
Except for extremely small releases of refrigerant such as those that occur when disconnecting
service hoses (diminutive release), a technician who knowing releases or vents refrigerant to the
atmosphere is in violation of these regulations. Freon purchasers must be certi ed technicians and
have a valid EPA certi cation card.
4.5 Important Refrigeration Components
4.5.1 Expansion Valve
Each refrigerant circuit has an adjustable thermo-expansion valve (TXV). They are factory adjusted
to their nominal rating. Any eld adjustment should be to “ ne tune” a system that has been stabi-
lized and already has acceptable operating parameters.
4.5.2 High Pressure Cutout Switch
Each refrigeration circuit is protected by a high head pressure cutout switch with a manual reset
button. The switch is located near the compressor.
The pressure rating for R-407C systems is 450 PSIG.
The pressure rating for R-410A systems is 575 PSIG.